Empirical Wavelet Transform Based Method for Identification and Analysis of Sub-synchronous Oscillation Modes Using PMU Data
Loading...
Date
2024
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE-SGEPRI(State Grid Electric Power Research Institute)
Abstract
This paper proposes an empirical wavelet transform (EWT) based method for identification and analysis of sub-synchronous oscillation (SSO) modes in the power system using phasor measurement unit (PMU) data. The phasors from PMUs are preprocessed to check for the presence of oscillations. If the presence is established, the signal is decomposed using EWT and the parameters of the mono-components are estimated through Yoshida algorithm. The superiority of the proposed method is tested using test signals with known parameters and simulated using actual SSO signals from the Hami Power Grid in Northwest China. Results show the effectiveness of the proposed EWT-Yoshida method in detecting the SSO and estimating its parameters.
Description
Keywords
Empirical wavelet transform (EWT), sub-syn‐ chronous oscillation, Prony-based method, Yoshida algorithm, variational mode decomposition, phasor measurement unit (PMU).
Turkish CoHE Thesis Center URL
Citation
WoS Q
Scopus Q
Source
Volume
12
Issue
1
Start Page
34
End Page
40